EBS1W

    ACB

    1. Ambient temperature:-5~+40℃, the average value cannot exceed to +35℃ within 24h

    2. Altitude:2,000m

    3. Relative humidity:95%

    4. Pollution level:II.

    5. Installation location:Mount on the place where has no obvious vibration or impact



Function

EBS1W model universal type circuit breaker ACB applied to AC 50Hz, power conversion system rated insulation voltage 1000V, rated current 1000~6300A, has the dual-power supply system. When one fails to power, the automatic conversion between the guarantee the power supply reliability and security. The air circuit breaker ACB has fixed and drawer type.

 

Technical Parameter

Model type


EBS1W

Standard


IEC60947-1, IEC60947-2 and IEC60947-4-1

Poles


3P, 4P

Rated current In(A)


Up to 6300A

Rated insulation voltage Un(V)


1000V

Making time (ms)


30

Electrical life (times)


6,000

Mechanical life (times)


10,000

Breaking capacity


100kA

Rated Current of N-pole


100% In

 

Features

Compact structure

High breaking capacity 

No arcing distance and high safety 

With complete and reliable intelligent protection functions

Integration communication, compatible to many protocols

Simple installation, horizontal or vertical connection for main circuit

Many accessories are available

 

Ordering Note: 

Protection Type

Rated Current

No. of Poles

Breaking Capacity

Frame Type